Modèle: FKN-12
No. | Name | Unit | FKN12A | FKRN12A | ||
1 | Rated voltage | KV | 12 | 12 | ||
2 | Rated frequency | Hz | 50 | 50 | ||
3 | Rated current | A | 630 | 125 | ||
4 | Rated insulation level | power frequency withstand voltage(1min) | To ground,Interphase | KV | 42 | 42 |
breaker fracture | 48 | 48 | ||||
lighting implus withstand voltage(peak) | To ground, Interphase | 75 | 75 | |||
breaker fracture | 85 | 85 | ||||
5 | Rated short-time withstand current(thermal stability current) | Load switch | KA | 20 | ||
Grounding switch | 20 | |||||
6 | Rated short-circuit duration(thermal stability time) | Load switch | S | 4 | ||
Grounding switch | 2 | |||||
7 | Rated short circuit closing current(peak) | 50 | ||||
8 | Rated breaking current | load breaking current | A | 630 | ||
closed loop breaking current | 630 | |||||
Cable charging current | 10 | |||||
breaking no-load transformer capacity | KVA | 1250 | ||||
9 | Rated short-circuit breaking current(Current limiting fuses) | KA | 31.5 | |||
10 | Rated transf current | A | 1200 | |||
11 | Mechnical life | times | 2000 | 2000 | ||
1 | Fracture opening distance | mm | ≥175 | |||
Interphase center distance | 210±2 | |||||
interphase air distance | ≥ | |||||
travel | 210±4 | |||||
overtravel | ≥40 | |||||
2 | three-phase non-simultaneity of contact closing | ms | ≤0 | |||
three-phase non-simultaneity of contact opening | ≤5 | |||||
Proper release of shunt release | 40~65 | |||||
3 | Dominant loop resistance | μΩ | ≤130 |
Groupes de Produits : Disjoncteur à vide