nouveaux produits
Trouver Pôle Intégré, Type De Pôle Intégré Vcb, Disjoncteur à Vide dans le répertoire Industry, Reliable Fabricant / Fournisseur / Factory de Chine
Modèle: FZN63
No. | Name | unit | vacuum load switch | vacuum load switch -Fuse combination | ||
FZN63-12D/T630-25 | FZ63-12D/T1250-25 | FZRN63-12D/T200-31.5 | ||||
1 | Rated voltage | KV | 12 | |||
2 | Rated frequency | HZ | 50 | |||
3 | Rated current | A | 630 | 1250 | 200 | |
4 | Rate short-time withstand current | KA | 25 | |||
5 | Rate withstand current(peak) | KA | 63 | |||
6 | Rated short-circuit closing current | KA | 63 | 82 | ||
7 | Rated active load breaking current | A | 1250 | |||
8 | Rate closed loop breaking current | A | 1250 | |||
9 | breaking no-load transformer | KVA | 2000 | |||
10 | earth fault current | A | 20 | |||
11 | Line under the earth fault conditions and cable charging current | A | 20 | |||
12 | Rated short-circuit breaking current | KA | 31.5/50(Depending on the fuse) | |||
13 | Ratedd handover/transfer current | A | 3150 | |||
14 | Settling time | ms | 45 | |||
15 | Power frequency withstand voltage 1min | KV | To ground,Interphase,vacuum breaker fracture:42, Isolate the fracture:48 | |||
16 | Lighting implus withstand voltage | KV | To ground,Interphase,vacuum breaker fracture:75, Isolate the fracture:85 | |||
17 | Mechnical life | times | >10000 |
Groupes de Produits : Disjoncteur à vide